Products

VCM-EN in Non Explosion-Proof Enclosure

MPS’ most popular model. Applicable to Utility, Industrial, Hydro and all Rotating Machinery where monitoring of shaft current and shaft voltage on one unit is required.

For the most complete protection on large, or  critical machines, the VCM-E is the perfect choice. With higher shaft current measurement capacity, uninterrupted grounding, continuous monitoring via 4-20mA signals and alarms,  operators are alerted to conditions such as brush performance failure or high voltage/current.  VCM-E’s continuously monitor shaft voltage and/or grounding/earthing current providing three 4‑20 mA output signals (per VCM-E) for remote monitoring and trending.

 

  • Continuous Train Performance Sensing and Tracking
  • Continuous Train Trending Aiding in Maintenance Scheduling
  • Alarms when shaft grounding devices have lost contact with the shaft.
  • Alarms on high and low grounding current and/or high shaft voltage.

Early Warning of:

  • Shaft Grounding
  • High Residual Magnetism
  • High Static Electricity
  • Shaft or Rotor Rubs
  • Electrical Machinery Defects

 

OUTPUTS per VCM-E:  
Monitoring:  
Local: 3½ digit liquid crystal display indicating Peak Current, Average Current, Peak Shaft Voltage** and Power/Alarm Check, selected with rotary switch.
Remote: 4 to 20 mA signal representative of Peak Grounding Current; 4 to 20 mA signal representative of Average Grounding Current.;4 to 20 mA signal representative of Peak Shaft Voltage.**
Alarms :  
Local: LED for minimum and maximum grounding current and maximum shaft voltage.**
Remote: Open contact on minimum and maximum current, maximum voltage and loss of power supply to the unit.  (User selectable latching is optionally available in Non-Explosion-Proof Enclosures Only)
INPUT per VCM-E: Ground Current Lead (from shunt in grounding device circuit). Voltage Lead (from separate voltage sensing device/system).                                                 PLEASE NOTE: MPS VCM's will operate with any Vendor’s Shaft Grounding or Voltage Sensing Devices
POWER REQUIREMENTS: 100 VAC to 240 VAC, 60/50 Hz.
HARDWARE REQUIREMENTS: 100 mV shunt for 1, 2, 5, 10, 20, 50, 100, or 200 Amps (MPS supplied).
TEMPERATURE:  
Operating: -10°Cto 50°C (14°F to 122°F)
Storage: -23°Cto 60°C (-10°F to 140°F)
Relative Humidity: 0%to 95%, non-condensing

Order Codes:

VCM-EN

Dimensions:

Height:: 4.3 in. (109 mm)
Length: 7.4 in. (190 mm)
Width: 7.8 in. (198 mm)
Weight 3 lbs. (1.36kg)

SAFEGUARDING MACHINERY WORLDWIDE SINCE 1980.

800-647-7372