VCM Rack Mount Solutions
VCM Rack Mounts offer easy integration with other monitoring equipment. This option comes with the ability to monitor 1,2,3 or 4 separate units in one enclosure. The rack mount version with VCM-E circuitry, will fit into any standard 19" rack. The VCM-E circuitry allows continuous monitoring of your rotating machinery(s) shaft both locally (LCD display) and remotely (4-20 mA outputs) of Peak and Average Current and Peak Voltage. With the multi-configurable options, it is like having up to 4 separate VCM-E's in one enclosure.
Get Early Warning of:
- Loss of Shaft Grounding
- High Residual Magnetism
- High Static Electricity
- Shaft or Rotor Rubs
- Electrical Machinery Coil and Core Problems
|
OUTPUTS per VCM-E: |
|
|
|
Monitoring: |
|
|
|
Local: |
3½ digit liquid crystal display indicating Peak Current, Average Current, Peak Shaft Voltage** and Power/Alarm Check, selected with rotary switch. |
|
|
Remote: |
4 to 20 mA signal representative of Peak Grounding Current; 4 to 20 mA signal representative of Average Grounding Current.;4 to 20 mA signal representative of Peak Shaft Voltage.** |
|
|
Alarms : |
|
|
|
Local: |
LED for minimum and maximum grounding current and maximum shaft voltage.** |
|
|
Remote: |
Open contact on minimum and maximum current, maximum voltage and loss of power supply to the unit. (User selectable latching is optionally available in Non-Explosion-Proof Enclosures Only) |
|
|
INPUT per VCM-E: |
Ground Current Lead (from shunt in grounding device circuit). Voltage Lead (from separate voltage sensing device/system). PLEASE NOTE: MPS VCM's will operate with any Vendor’s Shaft Grounding or Voltage Sensing Devices |
|
|
POWER REQUIREMENTS: |
100 VAC to 240 VAC, 60/50 Hz. |
|
|
HARDWARE REQUIREMENTS: |
100 mV shunt for 1, 2, 5, 10, 20, 50, 100, or 200 Amps (MPS supplied). |
|
|
TEMPERATURE: |
|
|
|
Operating: |
-10°Cto 50°C (14°F to 122°F) |
|
|
Storage: |
-23°Cto 60°C (-10°F to 140°F) |
|
|
Relative Humidity: |
0%to 95%, non-condensing |
|
Order Codes
VCM-RM1, VCM-RM2, VCM-RM3, or VCM-RM4
Dimensions
Height: 5.2 in. (133 mm)
Length: 14.8 in. (375mm)
Width: 19 in. (482.6 mm)
Weight: 25 lbs. (12.7 kg) for VCM-RM1
(Add 3 lbs for each additional VCM-E)