VCM Rack Mount Solutions
Overview
VCM Rack Mounts offer easy integration with other monitoring equipment. This option comes with the ability to monitor 1,2,3 or 4 separate units in one enclosure. The rack mount version with VCM-E circuitry, will fit into any standard 19" rack. The VCM-E circuitry allows continuous monitoring of your rotating machinery(s) shaft both locally (LCD display) and remotely (4-20 mA outputs) of Peak and Average Current and Peak Voltage. With the multi-configurable options, it is like having up to 4 separate VCM-E's in one enclosure.
Key Benefits
Get Early Warning of:
- Loss of Shaft Grounding
- High Residual Magnetism
- High Static Electricity
- Shaft or Rotor Rubs
- Electrical Machinery Coil and Core Problems
Specifications
TEMPERATURE: |
|
Operating Temperature Range:
|
-10°C to 50°C (14°F to 122°F) |
Relative Humidity: | 0% to 95%, non-condensing |
Storage Temperature Range: | -23°C to 60°C (-10°F to 140°F) |
POWER REQUIREMENTS: |
100-240 Vac 50/60Hz input into the MPS supplied power supply. |
INPUT: |
|
Current: 100mV | (use shunt with 100mV/ full scale rating) |
(Max. input voltage equals +/-10V) | |
Voltage: | +/- 1V (Max. input voltage equals +/-5V) |
+/- 10V (Max. input voltage equals +/-50V) | |
+/- 100V(Max. input voltage equals +/-300V) | |
Frequency Response: |
30 Hz to 10KHz |
OUTPUT: |
|
Monitoring: | |
Local: | 3½ digit liquid crystal display, indicating Average Current, Peak Current, Peak Voltage, and Power/Alarm Check, selectable with rotary switch. |
Remote: | 4 to 20 mA (Load impedance not to exceed 500 ohm) signal representative of Peak Current.* |
4 to 20 mA (Load impedance not to exceed 500 ohm) signal representative of Average Current.* | |
4 to 20 mA (Load impedance not to exceed 500 ohm) signal representative of Peak Shaft voltage.* | |
Alarms: | |
Local: | LED’s for high and low current and high voltage.* |
Remote: | Unified, single relay opening (10 watts, 0.5 A and 100 Vdc) (100Ω minimum load) for high & low current and high voltage.* |
NOTE: Maximum shaft current is equal to shunt rating. Maximum shaft voltage is 1, 10, or 100 V (selectable). | |
DIMENSIONS: |
|
Length: | 14.8 inches (375 mm) |
Width: | 19.0 inches (482.6 mm) |
Height:: | 5.2 inches (133 mm) |
Weight: | 25.0 pounds (12.7 kg). Add 3 pounds for each additional monitor added to rack. |
*For shaft current monitoring and alarm, a 100 mV current shunt for 1, 2, 5, 10, 20, 50, or 100 A is required. | |
For shaft voltage monitoring and alarm, a shaft voltage sensing device is required. |
Order Codes
VCM-RM1, VCM-RM2, VCM-RM3, or VCM-RM4